This product is available through direct order only
Please call (702) 370-2481
The simplified version of the Brick Wall Series Mode Protectors, the PWOM15 is a module unit. Created to be designed into original equipment, this unit has proven valuable in various applications from highway signs to data acquisition systems. By allowing an OEM to design a Brick Wall unit into their product, both the manufacturer and their customers are insured of the best in surge protection.
Outlets Available | None, this unit has a terminal strip for connection. |
Load Ratings | 15A at 120 volts, single phase, 50-60 Hz; full load regulation 1%. |
Endurance Test | 1,000 surges of 6,000 volts, 3,000 amperes, SRV <400 volts, no failures, L-N (ground wire protection) mode, U.S. Gov't. Mode 1. |
Limiters | Series surge reactor current limiter; cascaded, auto-tracking dual polarity voltage limiters; dual pulse inverters. Parameters optimized for switch-mode power supply protection. |
Clamping Voltage Onset | 172 volts nominal; 2 volts above peak line voltage (auto-tracking). |
EMI/RFI Filter Response | (bi-directional, wave tracking): With 50 ohm Rg load: 3db at 5kHz; 26dB at 100kHz; 38dB at 300kHz. |
Let-Through Slew Rate | 5,000 volt/microsecond disturbance reduced to 28v/microsecond within AC power wave envelope, and less than 10v/microsecond outside the power wave envelope. |
Maximum Applied Surge Pulse Joule Rating | Unlimited rating (due to surge current limiting) (8x20microsecond). |
Maximum Applied Surge Pulse Voltage | 6,000 volts (1.2 x 50 microseconds) (Industry Standard rating). |
Maximum Applied Surge Pulse Current | >100,000 amperes (unlimited due to current limiting) (8 x 20 microseconds). |
Endurance, C62.41-1991 (formerly IEEE 587) Category B3 (C1) pulses | 2kv>100,000; 4kv>10,000; 6kv>1,000 (NRTL verified). |
Dimensions | 3" H x 6.25" W x 7.2" D |
Weight | 2.75 lbs. |